Three-circuit Time Relay
VL-100А, VL-101А

VL-100А, VL-101А
Three-circuit time relay has instantaneous, passing and finite contacts. Such a kind of device is used with the time excerpts (delays) after giving (VL-100A) and after turning off the supply voltage (VL-101A).
The time relays (VL-100A, VL-101A) are intended for switching of electrical circuits with certain time excerpts, that are beforehand set in the protection devices, emergency control systems and industrial automatic equipment.
- Working temperature: - 40 °С … + 55 °С.
- Unified linkage and connection dimensions for the convenience of the relay mounting and service.
- The mounting with front / back wires connection.
- Step control of the actuation settings with discretization of 1% of the maximum value.
- For visual control and operative change relay actuation unitshave a transparent cover with a possibility of sealing.
- LED indication of the output relay actuation.
Working conditions
Closed housing in areas with a temperate and frigid climate.
Shaking effect:
- in the range of the frequencies of (5-15) Hz with an acceleration of 3 g;
- in the range of frequencies to 60 Hz with an acceleration of 2 g;
- in the range of frequencies to 100 Hz with an acceleration of 1 g;
- repeated blows by duration (2-20) ms with acceleration of 3 g.
Working position in the space – any.
Functional charts of work:
Technical characteristics
Power supply, input | VL-100А | VL-101А | |
---|---|---|---|
Voltage supply, V | Direct current | 24, 110, 220 | 110, 220 |
Alternating current | 100, 220, 380* | 100, 220, 380* | |
Allowable limits of the voltage supply | from 0,8 to 1,1 Urated | ||
Actuation voltage, V | (0,65-0,75) Urated | (0,65-0,75) Urated | |
Reset voltage, V | (0,4-0,5) Urated | (0,4-0,5) Urated | |
Power consumption, W (VA), not more than | 6 | 10 | |
Output | |||
Quantity of the circuits | 3 | 3 | |
Quantity of the change-over contacts (including * contacts of the instant action) |
1* + 1 + 1 | 1* + 1 + 1 | |
The range of the time settings уставок (according to modifications), s | 0,05-4,95 0,1-9,9 0,3-29,7 1-99 |
0,05-4,95 0,1-9,9 0,2-19,8 |
|
Excerpt control | by step | ||
Minimum time of repeated readiness, s | 0,1 | 0,1-0,3 | |
Reset time, s | 0,08 | Seton a scale | |
Switching voltage, V (direct and alternating current with frequency of 50 Hz) |
from 24 to 250 | ||
Switching currents, А | from 0,01 to 2 | ||
Switching power, VA(W) - in the circuit of alternating current - in the circuit of direct current |
300 VA at cosπ=0,5 60 W at τ=0,05 s and 30 Wт at τ=0,02 s |
||
Mechanical durability, cycles | 106 | 105 |
Electrical endurance makes up 50 000 cycles; off-load - 100 000 cycles.
Relays VL-100A, VL-101A are installed by means of projection mounting with front/back wires connection.