Auxiliary Electromagnetic Relay
PE46, PE46-1


PE46, PE46-1 - auxiliary relay
PE46

There are two-position relays (DC / AC) with switching on time not more than 0,03 s.

Application

The auxiliary electromagnetic relays PE46, PE46-1 are intended for using in the protection circuits, control and automation of the electrical power equipment for the switching of the electric loads in the DC circuit with rated voltage 24V…230V and AC circuit with rated voltage 24V…400V (50 Hz and 60 Hz).

Working conditions

The range of the working temperature: -40 °С…+55 °С.
Shaking effect:
- in the range of the frequencies to 15 Hz with an acceleration of 3 g;


- in the range of the frequencies to (15-100) Hz with an acceleration of 1 g.

Technical characteristics


Rated voltage of switched circuit, V:
     direct current
     alternating current

24 - 230
24 - 400
Minimum current of contacts, A:
     at a voltage of 24 V
     at a voltage of 110 V and more

0,02
0,01
Protection level:
     relay
     screw terminal

IР40
IР10
Insulation test voltage, V:
     among all electrically independent circuits, connected together, and relay enclosure
     among electrically independent circuits
     among open contacts of each contact sets
     between actuating and holding-upcoils

2 500
2 500
1 000
550
Isolation resistance of the dry and pure relay which wasn't in operation , МОм, not less:
     relay in cold condition
     relay in warm condition

20
6
Mechanical durability, cycles, not less 100 000
Electrical endurance, cycles, not less 50 000

Features

  • The number of contacts makes up 6 groups in different combinations (make and break contacts);
  • The actuating limit of the DC relay is within 0,5 -0,7Urated; the actuating limit of the AC relay is within 0,6-0,8Urated (it counteracts the false actuating of the relay);
  • The power consumption of the coils makes up not more than 6 W (for DC voltage), not more than 10 VA (for AC voltage), that provides the possibility of the switching-in/switching-off of the relay by means of low-power contacts of the instrument relays ;
  • The switching capacity of the relay contacts allows to control by the coils of the switching-in/switching-off of the vacuum and oil switches;
  • There is the possibility of the visual observation of a condition and movement of contacts without removal of the enclosure (there is a transparent cover in the location of contacts), and also in the version of using module via transparent enclosure;
  • Relay construction provides the mounting by means of projection mounting on a vertical surface with the fastening by the screw or on DIN-rail with front/back wires connection (in the same version without additional details, studs, etc.). Working position in the space – any;
  • Incombustibility and fire resisting property according to requirements for the devices which are not serviced during warranty period:
    - enclosure: to 650 °С;
    - terminal blocks and units holding current-carrying parts: to 960°С;
  • Taking into account the immunity to mechanical influences and main parameters, the relays are suitable for application on nuclear power plants;
  • Relay outputs allow to connect two wires with section 0,12‑1,5 mm² (solder contact) and 0,75‑2,5 mm² (screw terminal);
  • Relay contacts: make contacts and break contacts;
  • Connection circuits, outside dimensions, linkage dimensions, contacts combination (kind and quantity) of the relays PE46, PE46-1 correspond and provide possible replacement of the relays RP11, RP12, REP38D.

Benefits PE40-PE46

Benefits PE40-PE46

Outside dimensions


PE40-PE46 - outside  dimensions
Outside, linkage and connection dimensions of the relay (screw terminal)
with front/back connection of the wires


PE40-PE46 - outside  dimensions
The mounting on relay panel with screw terminal
and back conductors connection

Connection diagram


PE46, PE46-1 - connection diagram
(+) and (-) - signs of polarity of the connection for the actuating coil (1) and disconnecting coil (2);
а) relay PE46 (DC)


PE46, PE46-1 - connection diagram
(~) - the terminals for the connection of the actuating coil and disconnecting coil;
b) relay PE46 (AC)


PE46, PE46-1 - connection diagram
(+) and (-) - signs of polarityof the connectionfor the actuating coil (1) and disconnecting coil (2);
c) relay PE46-1 (DC)


PE46, PE46-1 - connection diagram
(~) - the terminals for the connectionofthe actuating coil and disconnecting coil;
d) relay PE46-1 (AC)


Relay Coil Parameter Parameter value Actuating
DC AC
PE46
PE46-1
actuating Urated, V 24 48 110 220 100 110 220
(230)
0,5...0,7 Urated DC
0,6...0,8 Urated AC
Ra, Оm 160 950 2450 5250 2000 2000 8800
Z, Оm - - - - 6000 6000 11000
Р, W (VA) 3,5 2,5 5 9 (2) (2,3) (5)
disconnecting Urated, V 24 48 110 220 100 110 220
(230)
Ra, Оm 240 1450 3450 5750 2000 2000 8800
Z, Оm - - - - 6000 6000 11000
Р, W (VA) 1 2 5 9 (2) (2,3) (5)

Convention structure of the type of the relay (PE40 – PE46) at the order

PE40 - type of the relay

At the order of the relay it is necessary to indicate additionally: rated voltage (Urated) and rated current (Irated) of the coils (look at the table above), the way of the external wires connection (front/back), the way of the relay mounting (DIN-rail, screw terminal). At the order of the module (separate from the relay) it is necessary to indicate the voltage of the relay coils (look at the table above).


PE40-PE46 - Mounting on the DIN-rail
PE40-PE46 - Mounting on the DIN-rail
Mounting on the DIN-rail
PE40-PE46 - additional module
Additional module