Centralized Alarm System Annunciator Device
RZL-05.CS


RZL-05.CS - centralized alarm system annunciator device
RZL-05.CS

advantage-rzl-05

Digital oscilloscope
Event log


advantage-rzl-05

Integration in
SCADA-system


advantage-rzl-05

Environment temperature
-40°C...+55°C


advantage-rzl-05

User-defined logics

Application

The RZL-05.CS is a microprocessor-based annunciator device for centralized supervision alarm systems of electrical substations, power plants and other facilities, equipped with relay protection and automation devices.

# Download the catalog. Relay Protection and Automation Devices.

Functions

Alarm function from discrete signals

  • Annunciator device for operation from NO or NC contacts.
  • Adjustable time delay.
  • LED-indication of each alarm channel.
  • Collecting signals from output contacts of relay protection and automation devices.
  • Alarm and warning signals receiveing with adjustable time delay, ensuring action repetition and visual (light) indication;
  • Receiving signals of the position of switching devices with visual (light) indication;
  • Receiving signals from auxiliary signaling buses with ensuring repeatability, visual (light) indication and diagnostics of auxiliary buses.

Group Alarm Functions

  • Receiving signals from signaling buses, in response to a sudden current changing, ensuring repetition of action, visual (light) indication.
  • Compatible with a wide range of typical configurations of supervision alarm auxiliaries.

Alarm reset functions

  • Local and remote alarm reset.

Functions for controlling external sound devices, etc.

  • Sound alarm control separately for alarm and warning circuits with the possibility of automatic reset with time delay.
  • Group and extended alarm signals, apart for emergency and warning alarms.
  • Critical and warning audible alarms separation.
  • Adjustable audible alarm length.

Registration function

  • Event reporting.
  • Nonvolatile memory of events logs and device settings.
  • Serial data transfer interface.

Technical parameters


Power supply units parameters
Operating voltage range, DC or AC 90 – 254 V
Power-on availability time 1 s
Operating supply interruption 0,5 s
Device burden 9 Wt
Number of independent power supply channels 1
Input current range continuously 2,5 - 20,0 A
Current input parameters
Rated input current 50 mA
Line current inputs number 4
Measurable current range 0,03 – 2,0 A
Input resistance 1 Ω
Maximum number of signals (I=50 mA) 30
Time delay settings range 0 - 99 s
Current thermal withstand, continuous/1s 2 / 10 A
Current input parameters
Rated input current 50 mA
Line current inputs number 4
Measurable current range 0,03 – 2,0 A
Input resistance 1 Ω
Maximum number of signals (I=50 mA) 30
Time delay settings range 0 - 99 s
Current circuits thermal withstand, continuous / 1s 2 / 10 A
Communication
Communication interface USB - 1 pcs,
RS-485 - 2 pcs
Data Protocol MODBUS RTU
Connection speed via USB, RJ-485 9600...38400 bps
Binary input parameters
Number of inputs 40
Rated AC, DC voltage 220 V
Response voltage level 132 - 176 V
Response time not less 40 ms
Current consumption at 220 V:
- power-on current
- continuous

20 mA
4 mA
Maximum voltage, continuous 310 V
Binary output (relay) parameters
Number of binary outputs 9
AC voltage trip 400 V
Maximum AC current 8 A (16 A for K1 output)
DC voltage trip 300 V
Maximum DC LR-circuit trip current 0,3 A
Other
Mounting type Flush
Device dimensions (WxHxD) 300x240x128 mm
LED indicators total / configurable 48
Operating ambient temperature range - 40 to + 55 °C
Maximum Humidity at 25 °C 98 %
Insulation resistance, more than 50 MΩ
Insulation overvoltage withstand,
Instantaneous / continuous
2,0 kV, 50 Hz
5,0 kV pulse
Weight, less then 5 kg


RZL-05.CS - wiring

Wiring diagram of external circuits to the devices RZL-05.CS